http://www.iec.ch/TC57/CIM#TapChangerTablePoint.g
Property cim:TapChangerTablePoint.g


type
ObjectProperty
comment
The magnetizing branch conductance deviation in percent of nominal value. The actual conductance is calculated as follows: calculated magnetizing conductance = g(nominal) * (1 + g(from this class)/100). The g(nominal) is defined as the static magnetizing conductance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.
domain
cim:TapChangerTablePoint
range
cim:PerCent
References

Generated with TopBraid Composer by TopQuadrant, Inc.