http://www.iec.ch/TC57/CIM#ExcIEEEDC3A
Class cim:ExcIEEEDC3A


type
Class [owl:Class]
comment
The class represents IEEE Std 421.5-2005 type DC3A model. This model represents represent older systems, in particular those dc commutator exciters with non-continuously acting regulators that were commonly used before the development of the continuously acting varieties. These systems respond at basically two different rates, depending upon the magnitude of voltage error. For small errors, adjustment is made periodically with a signal to a motor-operated rheostat. Larger errors cause resistors to be quickly shorted or inserted and a strong forcing signal applied to the exciter. Continuous motion of the motor-operated rheostat occurs for these larger error signals, even though it is bypassed by contactor action. Reference: IEEE Standard 421.5-2005 Section 5.3.
subClassOf
cim:ExcitationSystemDynamics
equivalentClass
cim:ExcIEEEDC3A.kv max 1 cim:PU
cim:ExcIEEEDC3A.te max 1 cim:Seconds
cim:ExcIEEEDC3A.efd1 max 1 cim:PU
cim:ExcIEEEDC3A.vrmin max 1 cim:PU
cim:ExcIEEEDC3A.trh max 1 cim:Seconds
cim:ExcIEEEDC3A.vrmax max 1 cim:PU
cim:ExcIEEEDC3A.exclim max 1 boolean
cim:ExcIEEEDC3A.ke max 1 cim:PU
cim:ExcIEEEDC3A.seefd1 max 1 float
cim:ExcIEEEDC3A.seefd2 max 1 float
cim:ExcIEEEDC3A.efd2 max 1 cim:PU
References

Generated with TopBraid Composer by TopQuadrant, Inc.